MGE Galaxy 3000 UPS System • Uploaded on Jun 06, 2017
8.3 Battery Configurations
There are different configurations for different battery types and backup time. Here, the batteries from VISION and
YUASA are selected. The backup times ranges from 1hours to 4hours for 20KVA UPS and from 1hours to 2hours
for 30KVA UPS, because of limitation of CLA power rating.
UPS Backup
time Number of blocks Type of blocks Capacity(10H)
1h 1×24 6FM55SGX 52Ah
10kVA 2h 2×24 6FM45X 2×42Ah
4h 2×25 6FM75X 2×74.5Ah
1h 24 6FM75X 74.5Ah
15kVA 2h 3×24 6FM45X 3×42Ah
4h 3×25 6FM75X 3×74.5Ah
1h 1×25 6FM90X 90Ah
20kVA 2h 3×25 6FM55X 3×52Ah
4h 2×26 6FM150X 2×144h
1h 2×25 6FM75X 2×74.5Ah
30kVA
2h 3×24 6FM100X 3×96Ah
Sheet. 4 the battery configuration with VISION battery
UPS Backup time Number of
blocks Type of blocks Capacity
(10H)
1h 2X24 NPL24-12 2X24AH
10kVA 2h 2×26 NPL38-12 2×35.3AH
4h 2×26 NPL65-12 2×60.5Ah
1h 1×27 NPL65-12 60.5Ah
15kVA 2h 2×24 NPL65-12 2×60.5Ah
4h 3×26 NPL65-12 3×60.5Ah
1h 1×27 NPL100-12 92Ah
20kVA 2h 2×24 NPL100-12 2×92Ah
4h 4×26 NPL65-12 4×60.5h
1h 3X24 NPL65-12 3×60.5Ah 30kVA
Problem locating: That's an internal failure, control GDEx, MIZx, CHAx.
Problem locating: That's an internal failure, control GDEx, MIZx, CHAx.