SOURCE: York 3phase compressor tripping on low currant microprocessor.
If the unit is single phasing this is not good for the compressor. Does the system have a phase monitor? If not I would suggest you put one in to save thousands of dollars on the replacement of the compressor. How is the oil level? I ask because this are not to run themselves out of oil.